Model |
|
CCB-18HR1 |
Indoor Power Supply |
V-Ph-Hz |
220~240/1/50 |
Cooling |
Capacity |
Btu/h |
18000 |
Capacity |
kW |
5.3 |
Input |
W |
75 |
Rated current |
A |
0.4 |
EER |
W/W |
2.68 |
Heating |
Capacity |
Btu/h |
20000 |
Capacity |
Kw |
5.9 |
Input |
W |
75 |
Rated current |
A |
0.4 |
COP |
w/w |
3.34 |
Indoor Fan Motor |
Model |
|
YDK-35T-4 1 |
Input |
W |
75 |
Capacity |
uF |
2.5 |
Speed (Hi/Med/Low) |
r/min |
1050/950/830 |
Indoor Coil |
Number of Rows |
|
2 |
Tube Pitch (a) x Row Pitch (b) |
mm |
21 x 12.7 |
Fin Spacing |
mm |
1.55 |
Fin Type |
|
Hydrophilic |
Tube Outside Dia and Type |
mm |
Φ 7 Inner grooved |
Coil length x height x width |
mm |
1791 x 168 x 25.4 |
Number of Circuits |
|
5 |
Indoor Airflow (High speed) |
m³/h |
700 |
Indoor noise level |
dB(A) |
43~48 |
Indoor Unit |
Dimension Body (W x H x D) |
mm |
580 x 580 x 275 |
Panel |
mm |
650 x 650 x 30 |
Packaging Body (W x H x D) |
mm |
745 x 675 x 375 |
Panel |
mm |
750 x 750 x 95 |
Net/Gross weight Body |
Kg |
25/27 |
Panel |
Kg |
2.7/4.0 |
Max Pressure |
MPa |
4.0 |
Refrigerant |
Type |
R410A |
Refrigerant Piping |
Liquid Side/Gas Side |
mm |
Φ 6.35/Φ12.7(1/4″+1/2′) |
Drainage Pipe |
mm |
DN25 |
Standard Controller |
|
Standard controller |
Operation Temperature |
°C |
16~32 |
Ambient Temperature |
Cooling |
°C |
18~43 |
|
Heating |
°C |
-7~24 |
Application Area |
|
m² |
20-35 |
Model |
|
COU-18HR1 |
Outdoor Power Supply |
V-Ph-Hz |
220~240/1/50 |
Cooling |
Capacity |
Btu/h |
18000 |
Capacity |
Kw |
5.3 |
Input |
W |
1900 |
Rated current |
A |
8.26 |
Heating |
Capacity |
Btu/h |
20000 |
Capacity |
Kw |
5.9 |
Input |
W |
1690 |
Rated current |
A |
7.35 |
Max Input Consumption |
W |
2500 |
Max Current |
A |
11.36 |
Starting current |
A |
40 |
Compressor |
Model |
|
ASH232SV-C8LU |
Type |
|
Rotary |
Brand |
|
Hitachi |
Capacity |
Btu/h |
18800 |
Input |
W |
1900 |
Rated current (RLA) |
A |
8.8 |
Locked rotar (LRA) |
A |
40 |
Thermal protector |
|
Internal |
Capacity |
uF |
60 |
Refrigerant Oil |
ml |
600 |
Outdoor Motor Fan |
Model |
|
YDK-38-6B |
Input |
W |
80 |
Capacity |
uF |
2.5 |
Speed |
r/min |
920 |
Outdoor Coil |
Number of rows |
|
2 |
Tube Pitch (a) Test Row Pitch |
mm |
25 x 21.65 |
Fin spacing |
mm |
1.7 |
Fin type |
|
Hydrophilic |
Tube outside dia. and type |
mm |
9.52 Inner grooved |
Number of circuits |
|
4 |
Outdoor Air flow (High speed) |
m³h |
2800 |
Outdoor noise level |
dB(A) |
53 |
Outdoor Unit |
Dimension (W x H x D) |
mm |
866 x 304 x 535 |
Packaging (W x H x D) |
mm |
920 x 335 x 585 |
Net/Gross weight |
Kg |
41/43 |
Refrigerant |
Type |
g |
R410a/1200 |
Throttle Part |
|
Capillary |
Design Pressure |
MPa |
4.0/1.2 |
Max Pressure |
MPa |
4.0 |
Connecting Wiring |
Outdoor power supply |
|
From indoor unit |
Power wiring |
mm |
3 x 1.5 |
Signal wiring |
mm |
5 x 1.5 |
Refrigerant Piping |
Liquid Side/Gas Side |
mm |
6.35/12.7 (1/4″+1/2″) |
Max Pipe Length |
m |
20 |
Max High Drop |
m |
10 |
Ambient Temp |
Heating |
°C |
-7~24 |
Reviews